|
Understanding the characteristics of fluorescent and HID lamps makes it
easier to recognize problems and simplifies corrective maintenance.
Lighting maintenance is easy; just replace burned-out lamps."
Unfortunately, that's a common attitude of those holding the corporate
purse strings. Of course there's more to lighting maintenance than lamp
replacement, particularly with discharge lamp systems. In fact, all
components of a lighting fixture come into play here. You need to clean
fixture enclosures and reflectors to prevent needless loss of useful light
output. Defective sockets and ballasts also need replacement. But, how do you know what needs replacement? What symptoms should you look
for? What troubleshooting techniques can you use? Read on to find out.
Symptoms of lighting system problems.
All discharge lighting systems offer visual (and sometimes audible) clues
when problems or failures exist. Usually, a problem affects only a few
fixtures in a total lighting layout. Here's what you should look for in a
lamp's appearance:
- Non-starting;
- On-and-off cycling;
- Extra-bright-light output; and
- Low-light output.
After identifying any abnormal fixtures, you have to find out which
component (lamp, ballast, fixture, or electrical supply) is the cause.
Select a normal and abnormal fixture. Then, with the electrical power off,
interchange the lamps. While doing this, look for differences in lamp
color, any broken lamp elements, burned or distorted bases, and defects in
the fixture itself. If you don't find any major differences between the
two, you should energize the lighting system. After they stabilize, observe
the light fixtures. If the "abnormal" appearance shifts to original "normal" system or fixture,
the problem is in the lamp; not the ballast, fixture, or system power
supply. Generally, your troubleshooting task won't be this simple, since more than
one factor usually contributes to component failure. For example, an
incorrect tap on an HID ballast can cause the lamp to fail prematurely.
Here, you should correct the wiring before you relamp the fixture.
Lamp troubleshooting.
Fluorescent lamps. When you energize a rapid-start lamp circuit, a
low-voltage transformer in the ballast provides cathode heating. At the
same time, you're applying a higher voltage (called the open-circuit
voltage) across the lamp. This voltage beginsarc conduction in the lamp.
Taking both voltage measurements is a good indication of proper ballast
operation. Fig. 1, left, shows how to make voltage measurements on a
two-lamp, series-type, rapid-start magnetic ballast. If only one cathode
gets the heating voltage, the lamp will fail to start or it will be slow
starting. This condition results from any one of the following:
- Improper contact in the holder;
- Broken holder;
- Open contact in a base pin;
- Broken base pin;
- Open cathode;
- Shorted leads in the base;
- Corrosion or foreign material on base pins or holder contacts;
- Defective ballast; or
- Improper wiring.
Heavy premature end darkening (usually at only one end) is a good
indication that one cathode is not properly heated and, therefore, the
heater circuit is incomplete. This isn't the same as gray or brownish bands
that occur about 2 in. from the lamp base (with the edge of each band on
the side nearer to the base being sharper). This latter symptom occurs when
the lamp's cathode coating wears out. While such bands may detract from the
appearance of the lamp, moderately dark bands have no significance in
regard to the life or performance of the lamp. The lack of cathode heating voltage can result from a poor connection
between lamp pins, lampholder contacts, or ballast leads and lampholder
terminals. Poor contact at the pins can result from improper lampholder
spacing in the lengthwise direction, with the lamp end held too tightly or
too loosely. For commonly used 3/8-in.-thick twist-type lampholders, the
back-to-back spacing of the lampholders should be 48 in., plus or minus
1/32 in. If the spacing is too tight, the weight of the lamps will ride on the face
of the base instead of the pins. Occasionally, a pin will slide behind the
clip instead of in front of it when you insert the lamp into the
lampholders. If the lampholders are too far apart, the pins may ride on the
edge of the lampholder rather than making contact along the full width of
the metal piece. Sometimes, installers remove end plates and other supporting devices
(needed to keep proper spacing) when installing fixtures in a row. This
looseness at the ends allows lampholders to bend away from the center. When installing lamps with exposed bi-pins, make sure the positioning guide
(an embossed mark on the metal end cap) is opposite the entrance slot of
the lampholder before inserting. Then, turn the tube 90 degrees. If
properly installed, HO and 1500mA lamps should have the boss or cover of
their recessed double-contact ends out of sight. With instant-start lamps, the two-lamp ballast circuit can be lead-lag or
series sequence design. A lead-lag ballast operates lamps in a parallel
circuit; meaning if one lamp fails, the other should continue to operate
properly. On the other hand, a series sequence ballast operates lamps in
series (meaning if one lamp fails the other will fail or glow dimly). A note of caution: Hybrid magnetic ballasts (developed as a bridge
technology between magnetic and fully solid-state electronic ballasts for
4-ft lamps) have components that cut off power to lamp cathode heaters
after the lamp ignites, resulting in an additional 2W saving per standard
lamp. As such, verify the type of ballast before measuring heating voltage. You should replace inoperative instant-start lamps as soon as possible.
When one lamp fails in a two-lamp series magnetic circuit, the second lamp
may continue to operate, but at a lower brightness. This condition reduces
the second lamp's life, causing a higher current to flow in the ballast.
The increased current, in turn, causes a rise in ballast temperature,
reducing ballast life and possibly initiating smoke. You should replace flickering instant-start lamps that show heavy end
blackening. This condition, known as lamp rectification, will cause a
reduction in ballast life if it continues. HID lamps. The electric arc of an HID lamp is much shorter and more intense
in photometric brightness than a fluorescent arc. An HID lamp often is
higher in wattage rating. This type of lamp has a specific warm-up time
when you first energize it. It also may require a specific operating
position; base-up, base-down, or base-horizontal. Because the size of the arc tube and mixture of materials in the tube
differ for each HID lamp type, each has its own operating and end-of-life
characteristics. These, in turn, relate to maintenance/troubleshooting
needs. The mercury-vapor (MV) lamp has the lowest efficacy of any HID source; most
of the MV lamps in the 100W to 1000W ratings have an average rated life of
24,000+ hrs. Because of this relatively long life (coupled with a slow
reduction in lumen output), you should replace these lamps well before they
reach their average rated life. Normal end-of-life (EOL) is a non-start
condition, or low-light output, caused by blackening of the arc tube from
electrode deterioration. The metal-halide (MH) lamp will drop in lumen output from 7% to 20% during
the first 100 hrs of operation, depending upon lamp wattage. Operating
conditions, such as lamp burning position and normal variations in supply
voltage or ballast characteristics, can affect lamp color and light output.
Using a universal burning MH lamp (instead of the original
position-specific lamp) when relamping a fixture may seem like a good
economic decision. After all, you can stock fewer lamp types. However, this
attempt at saving money is short-lived. An MH lamp, designed for a
particular operational position, can provide 10% to 15% more light and last
as much as 60% longer than the equivalent universal position lamp. Normally
at its EOL, an MH lamp won't start because the mix of materials in the arc
tube changes, along with the electrical characteristics. The ballast can no
longer sustain an arc. Both the 1000W and 400W lamps, when burned vertically, have a passive EOL.
The 1000W, 400W lamps, and all other wattages, when burned in other
positions, can fail in a way that causes the outer bulb to shatter. As
such, you should install these lamps in an enclosed fixture that contains
any glass, in case it shatters. A shrouded arc tube line of MH lamps has a
glass cylinder surrounding the arc tube to block any resulting glass
fragments from hitting the outer glass bulb and causing it to shatter. You
can use this latter type in an open fixture, where increased fixture
efficiency and lower-maintenance costs are important. (You can remove a
vertically mounted lamp from the fixture using a lamp-changing pole.) If
the outer bulb breaks or shatters in a safety line of MH lamps, power to
the lamp interrupts. However, the lamp's ability to self-extinguish does
not protect it against the danger of breakage. An indication of the high-pressure-sodium (HPS) lamp's normal EOL is on/off
cycling, since the aging lamp requires a higher voltage for operation than
the ballast can supply. The cycling can damage or destroy the starting
circuit and/or ballast. This is one of the most serious maintenance
problems in an HPS lighting system. You should replace a failed lamp
immediately, as this situation can also cause starting circuit damage. You should not remove an HPS lamp from a lamp socket for more than a short
period, unless you de-energize the circuit. You can damage the starting
circuit portion of the ballast, because the starting circuit will operate
continuously with the lamp removed. Some recent developments in HPS lamp technology aim at eliminating the
end-of-life cycling, especially in highway and street lighting. One product
has a positive end-of-life indicator, allowing you to identify and replace
lamps near the end of their service life. Instead of the usual on-again,
off-again cycling, this version of the HPS lamp goes out without any
cycling. This lamp version is also suitable for parking lot and garage
lighting. The low-pressure-sodium (LPS) lamp has a U-shaped arc tube and a two-pin
bayonet base. With the highest efficiency of HID light sources, its output
is a monochromatic yellow, so all colors appear as shades of gray, brown,
or black (except yellow objects). During its burning hours, the wattage
increases. For example, a 180W LPS lamp consumes 247W at 20,000 hrs. Keep
in mind any wattage or ampere reading taken on the branch circuit will
reflect this change of status condition.
Ballast troubleshooting. Fluorescent ballasts. It's difficult to measure
the output voltage of fluorescent ballasts in a luminaire because the
primary circuit of the ballast is automatically disconnected when you
remove an instant-start lamp. If you wire a replacement ballast to a
fixture, make sure all leads have a good electrical connection, especially
if the lampholders have "pressure lock" or "quick-wire" terminals rather
than screw terminals. If lamps in a fixture fail to light, improper wiring could also be the
cause. Sometimes you'll find leads without the insulation. In some cases,
you'll find two wires using one slot and, although there are two spring
clips inside the socket, both wires are set under one. It's good practice to examine the wiring of the ballast leads to make sure
it matches the diagram on the ballast label. At the same time, make a
visual inspection of the ballast casing. Leaking compound (except for a
small amount at the lead holes, which is normal), cracking or brittle
insulation, and discoloration on the can are all indications of ballast
approaching, or having reached, end of life. Remember, though a ballast
starts a lamp, this does not necessarily mean the ballast is functioning
properly. Short lamp life can result from ballast problems. HID ballasts. During operation, an HID ballast produces heat and usually
receives some heat from the lamp it serves. For that reason, its insulation
material can break down and cause a short in the core/coil windings.
Commonly, heat-caused deterioration will result in ballast winding or
capacitor failure; open or shorted. You can check an HID ballast using a multimeter, similar to checking a
fluorescent ballast. You should take specific safety precautions when
working on an HPS ballast. Make sure you disconnect this starter circuit,
since its high-voltage starting pulse can damage some multimeters. The
voltage on 50W through 400W lamps is at least 2500V; for the 1000W lamp,
it's at least 3000V.
You can make an open-circuit voltage and short-circuit current measurement
on an energized HID ballast. Here's how: With the lamp removed, use a true
rms voltmeter to measure the voltage at the socket. You can test the ballast capacitor with a suitable analog-type ohmmeter,
set at a high resistance scale. Turn off the branch circuit power first;
then discharge the capacitor by placing a screwdriver or other piece of
metal across its terminals. Now, you can disconnect the capacitor from the
circuit. Connect the meter's test leads to each terminal. If the ohmmeter
measures a high resistance, the capacitor is open and you should replace
it. If the reading is zero or a low resistance, the capacitor is shorted.
Again, you should replace it. If the reading is zero or a very low
resistance initially and the resistance slowly increases, the capacitor is
good. Also, make sure to check the voltage at the point of connection to the
electrical distribution system. Operation in an overvoltage state increases
wattage consumption and reduces the life of the ballast and lamp. The family of arc discharge lamps includes fluorescent and
high-intensity-discharge (HID) light sources. An electric arc struck
between two main electrodes or cathodes produces light in these lamps,
which are usually at opposite ends of the lamp. Discharge lamps usually operate with a ballast specifically designed to
provide the proper starting and operating voltage for the lamp. A ballast
changes the electrical characteristics of the power supply to those needed
by the specific lamp for it to start reliably. The ballasts provide the
open-circuit voltage, regulate the current (ampere flow) to the lamp, and
maintain the necessary operating voltage. Thus, you must match a discharge
lamp and ballast. You also have to properly connect them, operating within
specific limits. If you don't meet all of these conditions, the light
source won't work properly. You can divide the family of fluorescent lamps into the cathode preheat
type and those requiring no cathode heating or starters. Rapid-start (RS),
high output (HO), and 1500mA T12 lamps (along with the preheat type
requiring use of a starter device) all have similar characteristics. They
depend on the proper heating of cathodes to start and operate properly. You
can classify most of these lamp types under the heading of rapid-start
lamps. Instant-start and slimline lamps are two types that do not require the
heating of cathodes, nor do they use starting aids. The ballast
open-circuit voltage of these lamps is about three times the normal lamp
operating supply voltage. These will start and operate even when one
cathode is completely deactivated (which would be the end of normal life).
At that time, they usually show spiraling along the tube and occasional
orange-colored flashes. The figure, below, shows both rapid-start and
instant-start types.
|