|
The proper approach and knowledge of application issues is vital when
upgrading lighting systems. Energy savings and improved employee
productivity are the results of a good project. EC&M's April '99 issue features an article on lighting efficiency and how
to improve it. However, without understanding the possible consequences
when upgrading lighting systems, projects can end up badly. If the issues
addressed below are not considered, the results can be disappointing and
costly. Knowing the potential pitfalls and how to avoid them will lead to a
successful upgrade.
Ballast factor.
The biggest mistake made in lamp and ballast upgrades is failing to take
into account the ballast factor (BF). This aspect of lighting determines
light level; the higher the BF, the higher the light level. You should
select electronic ballasts based on the light level required, not on
maximum energy savings. It's common to choose a ballast with a low input
watts rating. When this is done, the ballast factor is usually too low,
producing a low light level. Although the initial light levels may seem
satisfactory when the lamps are new and surfaces are clean, over time, lamp
lumen depreciation and dirt depreciation factors will reduce the light
level, sometimes to a level that's too low. In 1-for-1 upgrades (with the same number of lamps and fixtures) from T12
lamps to T8 lamps, a ballast factor of 0.88 ensures equivalent light
output. If the old lighting system provides too much light, consider
reducing the light level by specifying a lower BF. To ensure lamp life
isn't affected, the lower limit for instant-start ballasts is 0.7. For
systems that produce too little light or where the number of lamps will be
reduced, consider a higher ballast factor to make up some of the light
loss. However, a higher ballast factor comes at the cost of higher power
input. The rapid-start ballasts have a higher input power because of the
additional power required to heat the cathodes. You can use ballasts with
BF up to 1.2 without fear of overdriving the lamps, and they can provide up
to 30% more light. Fig. 1 shows the relationship between power input and
ballast factor for rapid- and instant-start ballasts.
The color of light.
Correlated color temperature (CCT) is a numerical measurement of a lamps
color appearance. It's based on the principle that any object will emit
light if it's heated to a high enough temperature and the color of the
emitted light will shift in a foreseeable way as temperature increases. CCT
is based on the color changes of a theoretical "blackbody radiator" as it's
heated from a cold black to white-hot state. With increased temperature,
the radiator shifts gradually from red to orange to yellow to white and,
finally, to blue white. Therefore, a lamp's CCT is the temperature (in
degrees Kelvin) at which the color of the blackbody correlates with the
color of the lamp. Lamps with low color temperature are called "warm," while lamps with higher
color temperature are called "cool." These descriptions have nothing to do
with the temperature of the blackbody radiator, but rather refer to the
lamp appearance. Colors from the red/orange/yellow end of the spectrum are
described as warm and colors in the blue end of the spectrum are referred
to as cool. Looking at standard colors of fluorescent lamps, we see the
appearance is warm (3000K), cool (4100K), or neutral (3500K). Lamp CCT should match the type of activity occurring in the lighted area.
For offices, schools, and other work environments, designers usually choose
a cool lamp color (4100K). For stores, showrooms, and supermarkets, most
prefer a neutral color (3500K). Restaurants and lobbies usually use a warm
lamp color. Neutral (3500K) works well for most interior applications and
doesn't emphasize either end of the color spectrum. Avoid mixing lamp colors when upgrading lighting systems. For task specific
lighting, ensure the light source has the required portion of the color
spectrum you need. For example, if the visual task is sorting blue and
black objects, avoid incandescent sources, which are blue deficient. The color rendering index (CRI) is a system derived from visual experiments
and determines how colored objects appear when lighted. It uses eight
standard pastel color samples illuminated by the lamp and then by a
blackbody matched to the same color temperature. If no samples shift in
appearance, the lamp is rated at 100. If there is a shift, the result is a
lower CRI rating of the lamp. The CRI uses a relative scale; the higher its
value, the closer the lamp is to the standard colors. CRI values of 80 or above are high. A CRI of 75 works well for offices,
whereas, a CRI of 85 is recommended for high attention areas. Changes from
lamps with lower CRI values to lamps with high CRI may be perceived as "too
bright." This apparent increase in brightness commonly occurs with
one-for-one retrofits of 4-ft T12 lamps with 4-ft T8 lamps. The T8 lamp,
being smaller in diameter with the same lumen output as the T12, has a
higher surface brightness. In addition, because the CRI of the T8 lamp is
usually much higher than the T12 it replaces, the T8 is perceived to be
brighter. There is generally a high incidence of occupant complaints on one-for-one
upgrade projects that the lighting is "too bright." In these cases,
maintenance personnel usually solve the problem by removing one lamp.
Relighting projects, where new 3-lamp fixtures relight areas that formerly
used 4-lamp fixtures with T12 lamps, have fewer occupant complaints.
Lighting quality.
Productivity can be diminished in workspaces where lighting quality is low.
There is no one measure of lighting quality, but there are several issues
affecting this lighting component that you should recognize such as light
level, glare, visual comfort probability (VCP), veiling reflections,
flicker, and spacing criteria (SC).
Light level.
A host of issues must be given careful consideration before any hasty
conclusion is reached regarding the appropriateness of measured light
levels. These include, but are not limited to: the type of space and how
the space is used, flexibility of use, the desired lighting effects, the
visual tasks, owner's liability, and several weighting factors such as
occupants age, the importance of speed and/or accuracy in performing a
given task, and surface reflectance. A light meter is typically used to determine if light levels are
appropriate. These values can be compared with current recommendations made
by the Illuminating Engineering Society of North America (IESNA). These are
consensus recommendations made by lighting professionals. However, there
are no single value recommendations for any particular space or specific
task. In spaces that are overlighted, lighting requirements must be changed to
provide a lower level of light. For spaces that are found to be
underlighted (a common occurrence, in stairwells, where owner liability is
high), you should ensure that sufficient light is recommended for the
safety and security of occupants and visitors. Highlighting safety concerns
will strengthen your credibility. These unsafe conditions can become a
serious legal liability for you, your employer, or your client if not
addressed.
Glare.
Controlling glare produced by unshielded bulbs and tubes, and from poorly
shielded fixtures, is important to avoid loss of visual performance.
Smaller diameter lamps have higher bulb wall brightness that must be taken
into account to avoid lamp glare. The T5 lamps are best used in coves and
other indirect applications. Use louvers, such as those found on deep-cell
parabolic fixtures, to block lamps from view, or use low-glare acrylic
lenses to reduce surface brightness at high viewing angles. Indirect
fixtures reduce high luminance ratios in interior spaces by uniformly
lighting the ceiling cavity.
Visual comfort probability.
Visual comfort probability (VCP) is a rating of interior fluorescent
lighting systems that is expressed as the percent of people, who, when
viewing the system, find it acceptable in terms of discomfort glare. VCP
can be used to predict glare potential. You should select VCP values based
on the visual tasks. The IESNA recommended practice for office lighting
(RP1) recommends a minimum VCP of 70% for offices and 80% where there are a
lot of computers and screen glare needs to be reduced. VCP tables are
provided in fixture manufacturer's catalogs.
Veiling reflections.
Veiling reflections are reflections of incident light superimposed on
diffuse reflections. One common example is when you place a white paper on
the dashboard of a car. The image of the paper reflects on the windshield
and appears as a veil between the viewer and objects outside the car. A
similar condition occurs in interior lighting when lens fixtures are in
front of and above workstations. Lighting with well-shielded luminaries,
located perpendicular to and at sides of workstations, avoids veiling
reflections. Test sheets with special ink and paper are available to detect
this condition.
Flicker.
Flicker is produced by fluorescent or HID lamps when connected to magnetic
ballasts that turn lamps on and off 1202 per second. It can cause
distraction, eyestrain, fatigue, and nausea. Some people notice effects of
flicker more than others do, and it can be especially troublesome in
high-level lighting where industrial inspection is being performed. Use of
electronic ballasts that operate lamps at high frequency will eliminate any
perceptible flicker.
Spacing criteria.
Specular reflectors can affect lighting quality. Occupants often perceive
lack of quality lighting when retrofits are based on energy savings alone.
The problem is not that reflectors are used, but that they are not used
correctly. The incentive of a low first cost often drives the selection
process to commodity grade reflectors. These "one-size-fits-all" inserts
can be placed in nearly all four-lamp fluorescent 224 troffers, and two
lamps removed. However, in most cases, the remaining two lamps are not
relocated and the spacing criteria (SC) of the unit is severely reduced. When the SC of luminaries already mounted on wide centers (commonly found
in speculative buildings) is reduced, the effects are noticeable on walls,
and less noticeable between luminaries. The point at which the light
intercepts the wall is lowered when the S.C. of the units closest to the
wall is reduced. The result is that walls appear darker. The solution is to
either use custom reflectors or provide an asymmetrical designed reflector
in those luminaries located in rows closest to the walls. Custom reflector
designs do not reduce the SC. Using commodity reflectors results in dark
walls, and a dim environment, and most occupants do not believe that anyone
has improved their workspace.
Lamp life.
The average-rated life for lamps is defined as the point at which 50% of a
large group of lamps is still burning. A number of factors relate to lamp
life. Also to be considered is the time interval when lamps should be
changed. The lamp mortality curve (see Fig. 2, on the original article's
page 38) looks like the right hand side of a bell curve. The rating of fluorescent lamps is based on a test cycle of 3 hr/start (3
hr on, 20 min off). Most fluorescent lamps have an average-rated life of
20,000 hr (at 3 hr/start). For longer burn cycles (greater than 3
hr/start), average-rated life goes up. Burn cycle is the average length of
time a lamp operates each time it's turned on. Average-rated life is a
function of the number of times that a lamp is started. The calendar life of lamps is the time between lamp replacement and
includes the time lamps are turned off. For example, a standard F40 RS lamp
operated continuously results in an average-rated lamp life of 34,000 hr
(calendar life is the same; 34,000 hr4 3.9 yr). Turning off this lamp for
half of the time (12 hr/day), decreases rated lamp life to 30,000 hours,
but extends calendar life to 6.8 years. Out-of-tolerance line voltage (either too low or too high) can affect lamp
life. Short cycling lamps can also affect lamp life. Recent field
observations uncovered some causes for short life lamps, including
occupancy sensors set to short delay times (or left in the test mode), use
of instant-start ballasts in switching applications, or the combination of
short-delay time sensors and instant-start ballasts. Other causes are
sometimes mismatched lamps and ballasts.
Instant-start vs. rapid-start operation. With instant-start operation, an
external current doesn't heat the lamp cathodes. Electrons are supplied by
"stripping" them off the emissive coating of the cathode through the arc
discharge process. A "brute force" high voltage is applied across the lamp
to start it. The high voltage is necessary to initiate the discharge
between the unheated cathodes. Since the lamp cathodes are not heated,
instant-start operation results in lower electrical losses and the input
power to the ballast is reduced by approximately 2.5W per 4 ft lamp. The
disadvantage of instant-start operation is a reduction in average-rated
lamp life due to the rapid erosion of the cathode emissive coating,
especially at short burn cycles. When T12 lamps operate in an instant-start
mode they experience approximately a 25% decrease in lamp life than lamps
in rapid-start mode. Parallel lamp operation is the prevalent method of
wiring on instant-start ballasts. You can operate up to four lamps on
electronic, high frequency ballasts. In rapid-start operation, cathode heating is supplied by a separate set of
windings on the ballast, which adds approximately 2.5W/lamp. This
additional power reduces the efficiency of the system, but normal lamp life
is obtained, even with switching applications such as occupancy sensors.
Series wiring is the prevalent method of wiring lamps on rapid-start
ballasts. Rapid-start ballasts can normally operate up to three lamps per
ballast. For the two-lamp, rapid-start ballast, when one lamp fails the
second lamp will become dim, signaling that it is time to change the lamps.
A few rapid-start, electronic ballast designs operate the lamps in parallel
to eliminate the problem of lamps dimming when the second lamp fails. The choice of rapid-start or instant-start operation usually relates to the
application. If the application has long burn hours, and little switching,
then an instant-start ballast is the best choice. However, when there is a
lot of switching, the rapid-start ballast is the better choice. When
converting from rapid-start to instant-start ballasts, ballast
manufacturers advise shorting the socket (or using an internally shorted-J
socket) to avoid dramatically reduced lamp life. Instant-start operation
only requires one pin and bi-pin sockets should be shorted so they appear
to the ballast as one pin.
Harmonics.
Some harmonic distortion is produced by lighting equipment. The line
current can flow at the fundamental frequency (60 Hz in the U.S.) or it may
be combined with harmonic currents (multiples of the fundamental) such as
180 Hz (3rd harmonic). Harmonics are generated by core and coil ballasts
due to saturation of the magnetic steel core. This power deformation is
usually in the range of 12% to 22% total harmonic distortion (THD).
Specification of equipment having less than 20% THD is advised. However,
when ballasts with a THD that is lower than 10% are specified, a new
problem can be created, inrush current. The low impedance of electronic ballasts rated with THD less than 10%
creates inrush current. The problem is compounded when several ballasts are
on the same lighting circuit. Although inrush current is of very short
duration, the inrush peak current of an active front-end ballast can be
1002 or more its operating current. For passive front-end designs that
incorporate a series input choke coil, the inrush peak current is about 302
the operating current. The actual magnitude of the inrush current depends
on several factors, including the electrical characteristics of the
lighting circuit and where the switching occurs. The effects of inrush are usually long-term caused by the arcing of
metallic contacts that promotes contact erosion that eventually causes them
to weld together. Occupancy sensor contacts and building management system
lighting relays are the most commonly affected switching equipment. Most
occupancy sensors have been redesigned to incorporate zero-crossing relays
to prevent the problem. Zero-crossing relays sense the 60 Hz waveform of
the power line and delay closing the contacts until the next zero crossing.
No current flows at zero, preventing inrush.
Transient protection.
Electronic ballasts are sensitive to the surges and spikes normally found
in building power distribution systems. Many of the failures of early
electronic ballast designs have been attributed to a lack of transient
suppression. Most electronic ballasts now have some degree of protection
built in.
ANSI/IEEE Standard C62.41 addresses surge-withstand provisions. This
standard defines a set of test waveforms. However, internal protection may
not be sufficient for some situations. For example, for those facilities in
areas experiencing high lightning activity, a separate transient voltage
surge suppressor (TVSS) is recommended. A practical location for this
protective device is at the lighting distribution center (breaker box).
Installations in high-rise buildings encountered failures from the large
transients created by elevator motors starting and stopping. You should
also protect these with surge suppressor devices located at the lighting
distribution center.
Avoiding common mistakes. There are several easy to use computer programs
for calculating desired light levels. But remember, design for maintained
light level instead of initial light level. Lamps depreciate in their light
output over time and light reflecting surfaces get dirty. These light-loss
factors must be taken into account. Consider a relighting project when
fixtures are very old or in bad condition or when they are no longer
meeting the lighting needs of the current visual tasks.
|