|
Understanding how fluorescent and HID lamps work makes problem solving and
corrective maintenance easier. If you work with arc discharge lamps, you know troubleshooting can be
tricky. It never fails: Your ingenious idea that solved yesterday's problem
doesn't work today. So how do you predict the unpredictable? You must get
to know these fluorescent and high-intensity-discharge (HID) light sources
inside and out to truly understand their behavior. Arc discharge lamps produce light by an electric arc struck between two
main electrodes or cathodes. With few exceptions, they must operate with a
ballast, designed to provide the proper starting and operating voltage for
the lamp. A ballast changes the voltage of power supply to what the lamp
needs to start reliably (provide the open circuit voltage), regulate the
current (ampere flow) to the lamp, and maintain the proper voltage to the
lamp during operation.
Usually, you know there's a problem with a discharge fixture when the lamp
(or lamps) shows one the following conditions: nonstart, cycle on and off,
extra bright light output, or low light output. Any one of these is reason
enough to deenergize the fixture and take a closer look. To help you
troubleshoot, we'll look at the fluorescent source first and then the HID
source.
Fluorescent lamp characteristics.
Fluorescent lamps can be divided into the rapid-start and instant-start
type (Slimline lamps that do not have cathode heating). Rapid-start (RS), high output (HO), and 1500mA T12 lamps all have similar
characteristics. They depend on the proper heating of the cathodes to start
up and operate properly. Slimline lamps do not use cathode heating. They use the ballast open
circuit voltage (which can be about three times the normal lamp operating
supply voltage) to start operation. When fluorescent lamps don't operate, the ballast may not be the culprit.
Therefore, before replacing the ballast, examine all components.
- Change or check lamps to ensure proper operation. As you remove them,
examine sockets to ensure proper and positive contact with lamp pins.
- If you used starters, check and replace each as necessary.
- Examine the ballast leads to make sure the connection matches the diagram
on the ballast label.
- Examine and test the ballast. Leaking compound (except for a normal small
amount at the lead holes), cracking or brittle insulation, or discoloration
on the can may indicate the ballast (especially an electromagnetic type) is
approaching, or has reached, the end of its life.
The Table (in the original article) offers general instructions for
troubleshooting when fluorescent lamps do not start.At the outset, we'll discuss two specific problems found in any type of
fluorescent system. We call the first cycling. The National Electrical Code
(NEC) requires most indoor ballasts to have a cutout device that protects
them from overheating. If high ambient conditions cause the ballast to
overheat, the thermal protection device's switch disconnects it from the
power supply; if the temperature at the ballast is reduced, the cutout
device closes, reactivating the ballast, thus restarting the lamps. If such
a cycling condition persists, you must find the cause of the high
temperature and correct it. We call the second condition swirling, where the light appears to swirl or
spiral inside the tube during operation. This normal occurrence can last
for a few hours with some new lamps when first energized. However, a cold
ambient temperature or low input voltage can also cause the problem.
Rapid-start (RS) systems. To measure the starting voltage of an RS ballast,
connect a voltmeter between the highest reading Red lead and Blue lead with
the lamp removed. See Fig. 2 (in the original article). Consider the
following example: For an F 40 T12 two-lamp ballast, the minimum starting
voltage is 256V. The minimum starting voltage for F96T12HO two lamp ballast
is 466V. For a F96T12VHO ballast, it's 470V. All numbers are for minimum
ambient temperature of 50DegrF. You should find these open circuit voltages
on the ballast's label. (Note: Electronic ballasts generally provide
starting voltages higher than their electromagnetic counterparts. You can
also find their open circuit voltages on the ballast's label.) To measure the filament voltage on a single lamp unit, read voltage between
Red-Red and Blue-Blue leads. For two lamp units, read voltage between
Red-Red, Blue-Blue, and Yellow-Yellow leads. For all 4-ft and longer RS
lamps, the filament voltage should be between 3.5V and 4.5V. Sometimes with
a two-lamp, RS series ballast only one lamp will light to full brilliance.
Refer to Fig 2 again (in the original article). If the lamp between the Red
and Yellow leads is lit and the other lamp is out, look for a pinched
Yellow lead. If the lamp between the Red and Yellow leads does not light
and the other one does, the cause is probably a short. Why is good contact of lamp pins with their sockets so important? When an
RS lamp circuit first energizes, the low-voltage winding of the ballast
provides the cathode heating. Shortly afterward, the open-circuit voltage
is applied across the lamp, or lamps, to begin arc conduction. If only one cathode heats up, either the lamp will fail to start or it will
be slow in starting. Heavy premature end-darkening, usually at only one
end, usually indicates one cathode is not getting proper heat. Therefore,
the heater circuit is incomplete. This is not the same as gray or brownish
bands occurring about 2 in. from the lamp base, with the edge of each band
on the side nearer to the base being sharper. These bands occur when the
cathode coating wears out. While they may detract from the appearance of
the lamp, moderately dark bands have no significance concerning either life
or performance of the lamp. However, you should replace failed RS lamps
promptly to avoid any possible ballast damage. The lack of cathode heating voltage can come from a poor connection, either
between the lamp pins and lampholder contacts, or between the ballast leads
and lampholder terminals. Improper lampholder spacing in the lengthwise
direction, with the lamp end held either too tightly or too loosely, can
also cause poor contact at the lamp pins. Measure the voltage at the socket
terminals to determine if adequate heater voltage is present. Sometimes, in high-humidity conditions, RS lamps may start slowly or not at
all, even though the cathodes are heated properly. This can result from
dirt on the lamps, which makes the silicon coating ineffective. It can also
be due to a poor silicon coating. If a new installation experiences random
starting under high-humidity conditions, low supply voltage or poor silicon
coating on the lamps is generally the cause. If you see the same poor
starting in high-humidity conditions on an older installation, the cause is
usually an accumulation of dirt on the lamps. In this case, just wash the
lamps. Why is the RS lamp surface condition so important? For the lamp to start
within the voltage range of the ballast, it is necessary to excite the gas
fill inside the lamp by means of an external voltage; thus the excitation
ionizes the gas fill. The capacitance between the lamp and reflector or
fixture channel assists this external excitation. Of course, you must bond
(connect) the metal fixture to the equipment grounding circuit, and operate
the ballast from a grounded electrical system. Any dirt or moisture coating
on the lamp can reduce this capacitance. If you experience random starting of RS lamps, check the fixture for proper
grounding. As previously stated, for completely reliable starting in RS
circuits, you must have a starting aid, defined as an electrically grounded
metal strip at least 1 in. wide extending the full length of the lamp. The
lamp should be within half in. of the grounded metal strip for 40W lamps
and smaller (three-fourths in. for T8 lamps) and 1 in. for higher output
lamps. The modified RS ballast, a version of the RS ballast, reduces power
consumption by a few watts, and operates the lamps similar to the standard
RS ballast. The only difference is: You reduce or eliminate filament
heating, after the lamps ignite, so the 3V to 4V cathode heating voltage
reading will not be measured during normal operation.
Slimline fluorescent systems.
We use two types of electromagnetic ballast circuits for two-lamp operation
of Slimline lamps. The Lead Lag Slimline circuit has two sections: one
called the lead section, consisting of an inductive coil and capacitor in
series with the lamp; the other section consists only of an inductive coil.
The ballast operates one lamp independently. So if one lamp becomes
inoperative, the other will still light. You measure starting voltage
between Red and White and Blue and White leads. A Series Sequence Slimline circuit is smaller and lighter than the lead lag
type and operates two lamps in series, with the lamps starting in sequence.
Measure starting voltage between Red and White leads. Insert lamp in Red
and White position, then read the voltage between Blue and Black. For an
F48T12 Slimline lamp, the starting voltage is 385V. The open circuit voltage of a Slimline ballast is high enough to start a
lamp with one lamp filament deactivated. The lamp will flicker and become
very black at one end. If you don't replace the lamp, the ballast will
overheat and fail. If one lamp of an electromagnetic Slimline ballast is
operating and the other is not, the temperature of the coil will rise and
possibly fail. This problem does not occur with an electronic Slimline
ballast, which operates the lamps in parallel.
HID lamp characteristics. The electric arc of HID lamps is much shorter and
has a higher photometric brightness than a fluorescent arc. The lamps are
also often higher in wattage ratings, and they may require a specific
operating position; base-up, base-down, or base-horizontal. Because the
precise size of the arc tube and mixture of materials in the tube differ,
each type has its own operating and end-of-life characteristics, which
often directly relate to maintenance/ troubleshooting concerns. The family
of HID sources includes:
Mercury-vapor lamp (MV).
With the lowest efficacy of any of the HID sources, most of these lamps in
the 100V to 1000W ratings have an average rated life of 24,000 hrs. Because
of this relatively long life, coupled with a slow reduction in lumen
output, you should replace them well before reaching their average-rated
life. Normal end-of-life (EOL) is a nonstart condition or very low light
output caused by blackening of the arc tube from electrode deterioration. Metal-halide lamp (MH).
Operating conditions, such as lamp burning position and normal variations
in supply voltage or ballast characteristics, can affect lamp color and
light output of MH lamps. Normally, at its end-of-life, an MH lamp won't
start because the mix of materials in the arc tube changes. Therefore, the
ballast can no longer sustain an arc.
High-pressure-sodium lamp (HPS).
Normal end of life indication is on/off cycling, since the aging lamp
requires a higher voltage for operation than the ballast can supply. This
cycling sequence is normal, but not desirable, since the cycling can damage
or destroy the starting circuit and/or ballast. Thus, you should check a
cycling HPS fixture without delay. Other conditions that cause cycling
include: a loose electrical connection, faulty internal electrical
connection to the lamp or at an outdoor installation, and severe fixture
vibration, causing lamp voltage to rise above operating limits.
Low-pressure-sodium (LPS).
This lamp, which features high efficacy but somewhat limited applications
because of its monochromatic yellow color, uses a U shaped arc tube and a
two-pin bayonet base. During its burning hours, the lamp's wattage
increases. For example, at 20,000 hrs, a 180W lamp draws 247W, so any
ampere reading will reflect this increase in wattage consumption because of
aging. When troubleshooting, look at the lamp, ballast, capacitor, ignitor
(if used), socket, and perhaps the entire fixture for indications of
excessive heat. Let's look at each fixture component separately:
Lamp.
Any cracks or holes in a lamp's outer jacket usually indicate a defective
lamp. The presence of some form of foreign coating or material on the
inside of the lamp's outer jacket can also indicate trouble. This can
appear as a light yellow (with an MH lamp) or a silver mirrored appearance
(with an HPS lamp). Remember, an HPS lamp will have some normal silver
appearance around the lamp base. But, if all, or most, of an HPS lamp's
outer jacket has that coating, there's usually a defect. Check the metal
parts making up the mount or support for the arc tube for separation or
damage. Also observe if the arc tube is cracked or broken. Another
procedure is to put an ohmmeter (at the highest setting) across the lamp's
center base contact and the base's screw shell. There should be no
continuity (it should be open). If the ohmmeter shows continuity, there's a
short in the base or mount, and the lamp will not operate. If these
procedures don't help you uncover the problem, you can confirm the lamp is
defective by putting it in a fixture known to be operational.
Ballast.
An HID ballast typically steps up the incoming line voltage to a higher
voltage to start the lamp. Thus, a common problem with a multiple-tap
ballast can be an incorrect tap connection for the line voltage available.
A defective core and coil ballast will usually show signs of its condition,
such as darkening of the case or cracked or crumbling insulation, which
definitely indicates excessive current flow or excessive heat buildup.
Because of its construction, an F-can or encapsulated ballast does not
allow you to see the winding. However, these two types often give off a
strong odor if they have burned or melted ballast windings. You can make
voltage measurements on an HID ballast, similar to a fluorescent ballast,
using a multimeter. When you replace a defective ballast, also consider
replacing the capacitor, ignitor (if used), and lamp.
Capacitor.
Generally, a capacitor fails by either shorting or opening. When a
capacitor shorts, it can damage the ballast, lamp, and/or cause excessive
current flow, which may cause a breaker to trip. This type of failure is
more typical in the older oil-filled (metal oval can) capacitor type than
with the dry metalized film (round plastic can) type or the non-PCB
oil-filled capacitors, which typically have an integral interrupter. A
metal can type capacitor may bulge when it fails, particularly if it
doesn't have an integral interrupter. Usually, you use a single capacitor in a ballast circuit. However,
sometimes a fixture has a pair of capacitors in the ballast compartment,
wired in parallel to increase the capacitance. Thus, a common error in the
field is the incorrect wiring of dual capacitors, which should operate in
parallel, as seen in Fig. 3, in the original article. Verify the rating
marked on the capacitor matches that on the ballast. Then, verify the
actual capacitance in microfarads (mf), by taking a measurement. If low
light output is the problem, the third rating to check is the mf tolerance
(5) percentage. Some capacitors have a tolerance of 510%. A 110% would
lower the wattage at which the lamps are operating. In applications where
assurance of light level is vital, capacitors with a tight tolerances, such
as 51%, are used (e.g. sports lighting applications). You can test a capacitor with an ohmmeter set at a high resistance scale,
after you turn off the branch circuit power and disconnect the capacitor
from the circuit. Of course, always safely discharge the capacitor first. If
the ohmmeter measures a very high resistance, the capacitor is open, so
replac
e it. If the reading is zero or a low resistance, the capacitor has a
short. You should also replace it. If the reading is zero, or if a very low
resistance shows initially, and the resistance slowly increases, the
capacitor is good.
Ignitor.
Some HID lamps require a high-voltage pulse, provided by an external
starting aid, to excite mercury ions in the arc tube initially. This
ignitor circuit produces a sharp impulse typically with a rating of 2500V
to 4000V. The ignitor emits this pulse for one millionth of a second, at a
minimum of once per half cycle, until the lamp starts, and then shuts off
when it senses a current draw. It will also pulse when a lamp fails or the
socket is empty. You can partially base ignitor life on the number of times
the unit pulses. For that reason, you should repair or deenergize a
nonoperating fixture as soon as possible. An oscilloscope with a proper
high-voltage probe can show the pulse. HPS and some newer MH lamps use an
ignitor as part of the ballast. We'll discuss this factor, because it can
cause a maintenance person to troubleshoot problems that don't exist.
Socket.
Because of the higher voltages carried and heat generated in its vicinity,
you should check the socket carefully for cracking of the ceramic housing
or discoloring of the metal parts. One note of caution: Manufacturers
configure many MH lamp sockets specifically for a particular type of lamp.
Thus, they should not accept any other type of MH lamp. MH sockets can
produce the following confusing situations:
Position-oriented mogul base (POMB) socket for MH lamps.
This type of socket fits a horizontal-burning lamp only, which has a bowed
arc tube. When operated with that orientation, it offers increased light
output. The lamp's screw-shell base has a protruding pin, about 1/4 in. in
length. This configuration allows you to install the lamp in a POMB socket
that has a slot to accept the pin, thereby ensuring proper burning
position. For easy identification, the POMB socket is yellow. Thus, a POMB
lamp will not screw all the way into a standard mogul base socket. Do not
attempt to cut, grind, or bend the pin to make the lamp fit. Altering the
pin may allow the lamp to descend further into the socket.
Extended husk medium-base socket.
You can use this type of socket for a special MH lamp in an open fixture;
one without a cover lens. Generally, you must use an MH lamp in a fixture
with a cover lens. This requirement is a safety measure in the rare event a
lamp ruptures or explodes at the end of its life. Over the past 10 years,
lamp manufacturers introduced medium-base MH lamps that have additional
protection inside the bulb, so you can use them in an open fixture. To
ensure proper lamp usage, the open fixture has a special socket that
accepts only an open-rated MH lamp. This socket is longer, and the opening
is narrower than a standard socket.
Open-rated mogul base socket.
In the last five years, certain MH lamps have required the use of a higher
voltage rated socket we call open-rated. An open-rated, mogul-base MH lamp
has an extended center contact on its base to fit into the cavity of a
corresponding open-rated socket. For easy identification, this pulse-start
socket, rated to withstand the up to 4000V pulse (open voltage) needed to
start to start the lamp, is pink. What is the purpose of an open-rated mogul base socket and an open-rated
lamp? Recently, MH lamp manufacturers extended "pulse-start" technology,
already used in metal-halide lamps 150W and smaller, to other portions of
their product line. Superior to the older pinched arc tube design, a
pulse-start lamp offers impressive improvements. It can operate at lower
ambient temperatures; about 10DegrF lower than the pinched body lamps
(140DegrF instead of 130DegrF), higher lamp efficacy (up to 110 lumens per
watt), improved lumen maintenance (up to 80%), and consistent lamp-to-lamp
color (within 100 degrees K). Smaller than a pinched arc tube, a
pulse-start lamp's arc tube uses an ignitor to create a high-voltage
starting pulse, as does an HPS lamp. While both types of lamps use a mogul
base, a pulse-start lamp's socket (and ballast) is incompatible with a
pinched tube MH lamp's socket (and ballast), and visa-versa. (See Fig.4, in
the original article.)
Heat.
Excessive temperatures can cause lamps, ballasts, capacitors, and ignitors
to fail prematurely. This condition can also affect light output. In
particular, high-wattage, compact fixtures using reduced jacket MH lamps
can have elevated temperatures. Good indicators of excessive heat include:
continual short life of components, cover lens with a discolored
appearance, defective ballast with charred windings, internal arc tube that
looks black, and bulged or bluish outer bulb of the lamp. Placing
construction material around an HID fixture may cause excessive
temperature, or create a condition that restricts air flow and traps heat.
Test measurements.
When troubleshooting, check the line voltage at the fixture, not at the
panel, to account for any voltage drop. In most cases, the supply voltage
should be within 10% of the rating for best operation. Some reactor
ballasts require the voltage to be 55% for proper operation. If the line
voltage exceeds the recommended range, erratic lamp and ballast operation
may result. Identify and correct the external cause of the low or high
voltage by running a larger gauge wire (if you find voltage drop to be the
problem), changing taps on a distribution transformer, or
balancing/adjusting the loads on multiphase power systems. Next, check the
open circuit voltage (OCV). OCV is the voltage potential across the lamp
socket and is higher than normal lamp operating voltage. This is because
you need a high peak-to-peak voltage to strike an arc for starting the
lamp. Read the OCV of an energized HID ballast by removing the lamp and
placing one alligator clip of a true rms voltmeter on the lamp socket's
center contact, and the other alligator clip on the screw shell of the
socket. Using a meter other than a true-RMS reading tester can lead you
incorrectly identify a ballast problem. If the OCV reading for the specific
ballast is not within range, check to see if the ballast is receiving the
correct line (input) voltage, and for a good connection of the correct
ballast tap. If both are correct, the problem is usually a
defective/marginal ballast or capacitor or an incorrect ballast/lamp
combination. Make sure you take specific safety precautions when working on an HPS
ballast or some MH units, since they use a high-voltage starting circuit
(the ignitor) to initiate arc conduction. Disconnect this starter circuit,
since its high-voltage starting pulse can damage a multimeter. The voltage
on 50W through 400W lamps is at least 2500V, and for the 1000W lamps at
least 3000V. Therefore, determine if an ignitor is part of the circuit, and
disconnect it before taking an OCV reading. A short-circuit current
measurement gives you the highest current the lamp could see. It can also
indicate if the ballast/capacitor combination is correct (or if the
ballast/capacitor is defective). To do the SCCM test, deenergize the fixture. Then, use a jumper lead with
alligator clips at each end to create a dead short on the secondary side of
the ballast; directly at the socket (the ballast acts as a choke and limits
the current). One end of the of the jumper clips to the center contact; the
other end clips to the screw shell. For maximum safety, use an HLR fuse
holder with a 10A GLR fuse in the test wire, because the ballast could have
an internal short. Although the fuse could blow, it usually doesn't. But
for the few times it might, this precaution could save you from serious
injury. While making sure your ammeter is not close to the ballast's
magnetic field, since it could distort readings, clip the ammeter around
the jumper wire. Next, energize the circuit, and take the reading. If the
reading doesn't fall within the specified range, check the ballast input
voltage and ballast wiring. If both are correct, the problem is probably a
defective/marginal ballast or capacitor or the incorrect ballast/lamp
combination.
|